Infeed
2.4 Line contactor control
Commissioning steps:
1. Connect the line contactor control contact to DI/DO 8
Note
The current-carrying capacity of the digital output must be observed (see SINAMICS
S120 Control Units and Supplementary System Components Manual). A contactor relay
may be required!
2. Parameterize DI/DO 8 as output (p0728.8 = 1).
3. Assign parameter p0738 the control signal for the line contactor r0863.1
4. Connect the line contactor feedback contact to DI/DO 9.
5. Assign p0860 an inverted input signal r0723.9.
6. Enter the monitoring time for the line contactor (100 ms) in p0861.
Function diagrams (see SINAMICS S120/S150 List Manual)
• 8938
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p0860
• r0863.0...2
• p0867
• p0869
58
Active Infeed - Missing enables, line contactor control
BI: Line contactor, feedback signal
CO/BO: Drive coupling status word / control word
Power section main contactor hold time after OFF1
Configuration sequence control
Function Manual, 11/2017, 6SL3097-4AB00-0BP5