Figure 10-5
The same signals (high-active) of each drive or drive group are logically linked by means of
AND operation. The different signals selected via p10039 are logically OR'ed. Result of
these logic operations is the "Safe State" for each drive group. You can find details in the
SINAMICS S120/S150 List Manual in function diagrams 2901 (Basic Functions) or 2906
(Extended Functions).
Each F-DO supports the interconnection of up to 6 signals by way of indexing (p10042[0...5]
to p10045[0...5]) and their output as logical AND operation.
Function diagrams (see SINAMICS S120/S150 List Manual)
• 2893
• 2894
• 2895
• 2900
• 2901
• 2902
• 2905
• 2906
• 2907
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Selecting the safe state (example, Extended Functions)
SI TM54F - fail-safe digital inputs (F-DI 0 ... F-DI 4)
SI TM54F - fail-safe digital inputs (F-DI 5 ... F-DI 9)
SI TM54F - fail-safe digital outputs (F-DO 0 ... F-DO 3),
digital inputs (DI 20 ... 23)
SI TM54F - Basic Functions control interface
(p9601.2/3 = 0 & p9601.6 = 1)
SI TM54F - Basic Functions Safe State selection
SI TM54F - Basic Functions assignment (F-DO 0 ... F-DO 3)
SI TM54F - Extended Functions control interface
(p9601.2 = 1 & p9601.3 = 0)
SI TM54F - Extended Functions Safe State selection
SI TM54F - Extended Functions assignment (F-DO 0 ... F-DO 3)
Safety Integrated Basic Functions
10.9 Control via TM54F
707