Step 2: Determine the voltage precontrol in several optimization runs
1. To activate voltage precontrol, enter a value of "100" into p1703.
2. Proceed as follows to determine the dead time of the current controller reference model:
– Activate p0340 = 4, and automatically calculate the closed-loop control parameters.
– Perform a One-Button-Tuning (Page 116) with p5271.4 = 1 and p5271.7 = 1
3. Measure a current controller setpoint step and correct the value p1703.
– Repeat the current controller setpoint step until the current actual value reaches the
Figure 4-29
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
- Or -
(p5300 = 1).
setpoint without any overshoot or undershoot (see the following sample displays).
Voltage precontrol p1703 too low
Servo control
4.21 Voltage precontrol
195