The limitation is effective for the following activities:
● Jog mode
● Processing traversing blocks
● Direct setpoint specification / MDI for positioning and setting up
● Reference point approach
● Stop responses due to alarms
Jerk limitation is not active when messages are generated with stop responses OFF1 / OFF2
/ OFF3.
Starting against a closed brake
Under EPOS, if the drive should start against a closed brake, for example, for a suspended
load, then the enable signal p0899.2 is briefly withdrawn. The drive pulses are canceled and
fault F07490 is output.
To avoid this happening, using p1513 activate a supplementary torque which corresponds to
the brake holding torque. As a result, after releasing the brake, the load cannot sag and the
drive remains in closed-loop control without fault F07490 being output.
Function diagrams (see SINAMICS S120/S150 List Manual)
• 3630 EPOS - Traversing range limits (r0108.4 = 1)
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p2571
• p2572
• p2573
• p2646
Software limit switch
• p2578
• p2579
• p2580
• p2581
• p2582
• r2683.0...14
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
EPOS maximum speed
EPOS maximum acceleration
EPOS maximum delay
CI: EPOS velocity override
CI: EPOS software limit switch, minus signal source
CI: EPOS software limit switch, plus signal source
CO: EPOS software limit switch, minus
CO: EPOS software limit switch, plus
BI: EPOS software limit switch activation
CO/BO: EPOS status word 1
Function modules
8.8 Basic positioner