Activate Know-How Protection - Siemens SINAMICS S120 Function Manual

Drive functions
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Basic information about the drive system
13.8 Know-how protection
Absolute know-how protection
If you remove password p7766 from the exception list, it is no longer possible to enter or
change the password for know-how protection.
You must reset the drive unit to factory settings in order to regain access to the drive unit's
adjustable parameters. When restoring the factory settings, you lose what you have
configured in the drive unit, and you must recommission the drive unit.
Extending the exception list
1. Using the
2. Go offline (
3. Using p7763, in the expert list, define the required number of parameters n (n = 1 ... 500)
of the exception list.
4. Save the project.
5. Go online.
6. Load the project to the drive unit using the
7. In p7764[0 ... n-1], assign the required parameter numbers to the indices of p7763.
You have extended the exception list for know-how protection.
13.8.3.2

Activate know-how protection

Requirements
Before activating know-how protection, the following conditions must be met:
● The drive unit has been fully commissioned.
● You have generated the exception list for know-how protection (see Maintaining the list of
exceptions (Page 979)).
● To guarantee know-how protection, you must ensure that the project does not remain at
the end user as a file.
Procedure
1. Connect the drive unit to the programming device.
2. Go online with STARTER.
If you have generated a project offline on your computer, you must load the project into
the drive unit and go online.
3. Select the required drive unit in the project navigator of your STARTER project.
980
symbol on the PC, back up the drive unit settings.
).
icon in order to make them effective.
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Drive functions