Function modules
8.14 Advanced Position Control (including Active Vibration Suppression)
Examples:
The diagram shows, as example, how an open APC circuit can be measured. The stability of
the control loop can be identified based on the amplitude reserve at the frequency where the
phase goes through -180° (in the example, at 200 Hz).
A damping effect is achieved, if, at the oscillation frequency (in the example, 18 Hz) the
phase is approximately at 0° - and at the same time the amplitude is in the vicinity of 0 dB.
Figure 8-33
APC without sensor on the load side (p3700 = 4) – open circuit
600
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Drive functions