Monitoring functions and protective functions
9.5 Thermal motor protection
The motor temperatures are calculated based on the motor measured values. The calculated
temperatures are indicated in the parameters:
● r0034 thermal motor load
● p0613 motor temperature model ambient temperature
● r0631 Motor temperature model stator iron temperature
● r0632 Motor temperature model stator winding temperature
● r0633 Motor temperature model rotor temperature
Table 9- 2
Parameter:
9.5.1.4
Function diagrams and parameters
Messages (see SINAMICS S120/S150 List Manual)
• F07011
• A07012
Function diagrams (see SINAMICS S120/S150 List Manual)
• 8016
• 8017
• 8018
• 8019
644
Important settings
Explanation:
p5390
Alarm threshold
If the model motor temperature (r0632) exceeds the alarm threshold, alarm A07012
"Drive: Motor temperature model 1/3 overtemperature" is output
p5391
Fault threshold
If the model motor temperature (r0632) exceeds the fault threshold, fault F07011
"Drive: Motor overtemperature" is output.
p5350
Boost factor
Defines the boost factor for the copper losses at standstill.
Drive: Motor overtemperature
Drive: Motor temperature model 1/3 overtemperature
Signals and monitoring functions - thermal monitoring motor, Mot_temp
ZSW F/A
Signals and monitoring functions - motor temperature model - 1 (I2t)
Signals and monitoring functions - motor temperature model 2
Signals and monitoring functions - motor temperature model 3
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Drive functions