Toshiba GR200 Series Instruction Manual page 983

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Environmental performance
Electromagnetic Environment
High Frequency
Disturbance /
Damped Oscillatory
Wave
Electrostatic
Discharge
Radiated RF
Electromagnetic
Disturbance
Fast Transient
Disturbance
Surge Immunity
Surge Withstand
Conducted RF
Electromagnetic
Disturbance
Power Frequency
Disturbance
Power Frequency
Magnetic Field
Conducted and
Radiated Emissions
†For differential mode, 'CMP_NUM' setting utilized.
IEC 60255-22-1 Class 3,
IEC 61000-4-18
IEC 60255-26 Ed 3
IEC 60255-22-2 Class 4,
IEC 61000-4-2
IEEE C37.90.3-2001
IEC 60255-26 Ed 3
IEC 60255-22-3,
IEC 61000-4-3 Level 3
IEC 60255-26 Ed 3
IEEE C37.90.2-1995
IEC 60255-22-4
IEC 61000-4-4
IEC 60255-26 Ed 3
IEC 60255-22-5
IEC 61000-4-5
IEC 60255-26 Ed 3
IEEE C37.90.1-2002
IEC 60255-22-6
IEC 61000-4-6
IEC 60255-26 Ed 3
IEC 60255-22-7
IEC 61000-4-16
IEC 60255-26 Ed 3
IEC 61000-4-8 Class 4
IEC 60255-26 Ed 3
IEC 60255-25
EN 55022 Class A,
EN 61000-6-4
IEC 60255-26 Ed 3
- 969 -
1 MHz burst in common / differential modes
Auxiliary supply and I/O ports: 2.5 kV / 1 kV
Communications ports: 1 kV / 0 kV
Contact: 2, 4, 6, 8kV
Air: 2, 4, 8, 15kV
Sweep test ranges: 80 MHz to 1 GHz and 1.4
GHz to 2.7 GHz.
Spot tests at 80, 160, 380, 450, 900, 1850 and
2150 MHz.
Field strength: 10 V/m
Field strength 35V/m for frequency sweep of
25MHz to 1GHz.
5 kHz, 5/50ns disturbance
Auxiliary supply and input / output ports: 4 kV
Communications ports: 2 kV
1.2/50µms surge in common/differential
modes:
Auxiliary supply and input / output ports: 4, 2,
1, 0.5 kV / 1, 0.5 kV
Communications ports: up to 1, 0.5 kV / 0 kV
3kV, 1MHZ damped oscillatory wave
4kV, 5/50ns fast transient
Sweep test range: 150 kHz to 80MHz
Spot tests at 27 and 68 MHz.
Voltage level: 10 V r.m.s
50/60 Hz disturbance for 10 s in common /
differential modes†
Binary input ports: 300 V / 150 V
Field applied at 50/60Hz with strengths of:
30A/m continuously,
300A/m for 1 second.
Conducted emissions:
0.15 to 0.50MHz: <79dB (peak) or <66dB
(mean)
0.50 to 30MHz: <73dB (peak) or <60dB (mean)
Radiated emissions
30 to 230 MHz: < 40 dB(uV/m)
230 to 1000 MHz: < 47 dB(uV/m)
Measured at a distance of 10 m
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grb200

Table of Contents