Frame earth Screw
Figure 4.5-1 Schematic diagram and relationship of PWS terminal block
CAUTION
Note: For installation, the user should connect the case earth screw labeled "E" to the
1
protective earth of the panel or others using earthing wire, such that its cross-
section is AWG9 or larger.
Note: The user can connect a cable to this terminal directly without a cable ferrule; hence,
2
the recommended cables are AWG14 and their stripping lengths are 10mm. Use "AI
2.5 -10 BU" ferrule for AWG14 when the user wishes to use a cable ferrule made by
PHOENIX CONTACT®.
Alpha-numeric reference of PWS. Sign "*" is
substituted for actual slot location number.
*
T
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Positive(+)
26
27
28
29
Negative(−)
30
31
32
33
Short-wire
34
35
36
37
Short-wire
38
39
40
E
FG
- 300 -
2
T
*
PWS
2
4
FAIL1
3
1
8
10
FAIL2
9
7
29
DC
30
/
DC
31
32
35
36
37
38
FG
1
E
Schematic diagram
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)