Toshiba GR200 Series Instruction Manual page 479

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Error LED and LCD error message
(ii)
The IED has LEDs and LCD screen† so that the automatic supervision function issues a result
for the LEDs and the LCD screen. When the IED is linked with the SAS, it is possible to
transfer the result for the LED and LCD screen using the communication system. Table 9.1-2
shows that which indicators are used for result generation in the function.
Table 9.1-2 Displays on LEDs, LCD, and SAS
Levels
0: No error
1: Serious
2: Serious (Comm.)‡
3: Minor
4: Alarm
5: Warning
†Note: For more information, see
‡Note: It depends on the degree of the communication failure.
§Note: If the "In service" has to be turned off while a minor error (level:3) is occurring, set
On for the setting [ErrorLED_cond].
The user can see a current error information in Monitoring sub-menu† on the LCD screen†
(see Figure 9.1-1); Table 9.1-3 shows the six detail information, which the user can examine
carefully using the hexadecimal number. When two or more errors occur at the same time, an
error code is given by the summation of the error codes. That is, when X and Y errors (e.g., X-
error-code '00000002' and Y-error-code '00000004') occur, the sum value '00000006' is screened.
CP1M(ROM/RAM) error
10:48
[Serious error]
[00000011]
[01234567]
[01234567]
[01234567]
[01234567]
[00000000]
Figure 9.1-1 Example error codes and detailed information on Diagnostics sub-menu
†Note: See Chapter
updated automatically. If new information is required, refresh LED screen again.
Table 9.1-3 Detailed information in Hexadecimal in the ROM and the RAM error (example)
Display
area
00000001: ROM read error
Top row
00000002: ROM RAM mismatch
Middle row
RAM address
Bottom row
RAM value
"In service" LED
On
Off
On
On (Off§)
On
On
Chapter User interface: Outline
C u r r e n t e r r o r i n d i c a t e d b y S u p e r v i s i o n
1/1
C u r r e n t l o c a l t i m e ( N o t E r r o r o c c u r r i n g t i m e )
E r r o r d e g r e e ( l e v e l ) d i s p l a y e d
D e t a i l e d i n f o r m a t i o n i n H e x a d e c i m a l d u m p
User interface: Monitoring sub-menu: Diagnostics
Meaning of the detailed information
Left column
- 465 -
"Error" LED
Error message on LCD
Off
On
On
On
Off
Off
7 6 5 4 3 2 1 0
[
] [
"Top left"
[
] [
"Middle left"
[
] [
"Bottom left"
Right column
ROM address
ROM value
(No information displayed)
6F2S1931 (0.20)
(Not displayed)
Displayed
Displayed
Displayed
Displayed
Displayed
Diagnostics
and
.
]
"Top right"
]
"Middle right"
]
"Bottom right"
. It will not be
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)

Hide quick links: