Toshiba GR200 Series Instruction Manual page 316

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

DC voltage monitoring
4.5.3
Threshold voltage for detection/non-detection of power error
(i)
DC voltage is monitored in the PWS and a power supply failure can be outputted for the
Automatic supervision function. The user should set the failure level of the PWS. See
Automatic supervision function
Table 4.5-5 shows the threshold voltages for detection/non-detection of the power error at the
level high and low. This also shows how to set them with a shunt connector.
Table 4.5-5 Threshold voltage for detection/non-detection of the power error
(a) In the case of DC rated voltage "110-250 Vdc"
Voltage level
High
Typical 170V
Low
Typical 85V
(b) In the case of DC rated voltage "24-60 Vdc"
Voltage level
High
Typical 34V
Low
Typical 19V
Figure 4.5-2 Location of JP4 on the PWS module
for more information.
Threshold voltage for detection/non-detection of the power error
Threshold voltage for detection/non-detection of the power error
- 302 -
How to set
3
Insert a shunt connector
2
to position"1-2" at JP4
1
3
Insert a shunt connector
2
to position"2-3" at JP4
1
How to set
3
Insert a shunt connector
2
to position"2-3" at JP4
1
3
Insert a shunt connector
2
to position"1-2" at JP4
1
6F2S1931 (0.20)
Chapter
Note
This is
default.
Note
This is
default.
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)