Toshiba GR200 Series Instruction Manual page 125

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Operation example of Command-transfer-trip
2.4.4
Figure 2.4-7 shows double busbars with a transfer busbar. Feeder4 is being operated as the
transfer busbar. Let us suppose CH6 receives a falling gas-pressure signal via PLC connection
point "COMTP_INIT_CH6" (Step 1). The CHs (i.e., CH1, CH3, and both CH5 and CH6) can
issue Command-trip signals to the TRC for tripping the local CBs of Zone A and Zone C (Step
2). If it is required to tripping the remote CB beyond Feeder4, and when the below feeder
configuration is observed in the Replica evaluation, the COMTP function can trip the remote
CB (i.e., the COMTP function can issue a Command-transfer-trip signal to the TRC function
at Step 3).
Zone A
Zone B
Zone C
(Transfer
CHs)
)
CB2
CB1
CH1
Feeder 1
Feeder 2
Step2
Figure 2.4-7 Example of Command-Transfer-trip
CB3
CB4
CH2
CH3
Feeder 3
Feeder 4
CB being
beyond Feeder 4
- 111 -
CH6
CBC
CH5
CH4
Coupler
Step3 CB Tripped
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
Step1
DS closed
DS open
CB closed
CB open
CBC Coupler CB