communication packets will not be received from the remote terminal. In order to
avoid the influence, we recommend the user to test bad receptions for a particular
IED using the GOSUBBLK function. As a result, testing will only affect the
particular IED under test i.e. all other terminals will not be influenced by the
tests.
Selection of a slave protocol
10.3.5
Figure 10.3-28 shows the sub menu to select a slave IEC61850 protocol. The user should select
IEC61850 using the [Slave Protocol]. Note that the user has to restart the IED (i.e., the user
has to switch the IED off and on) if the user has switched to a slave protocol from the others†.
Communication
10:48
1/3
LAN
>
USBCOM
>
SLAVE PROTOCOL
>
Figure 10.3-28 Slave protection for the IEC61850 (setting menu)
Note: This sample menu illustrates how to select the IEC 61850, so that we discuss
neither the inclusion of IEC103, DNP3.0, and Modbus nor the selection of those
protocols here. See Figure 10.1-1 to check the inclusion of the protocols in the IED.
How to supervise in 61850 communication
10.3.6
The IED can detect errors on the IEC 61850 communication. The feature is provided separately.
Automatic supervision: Supervision of setting data [Commslv error]
(See Chapter
SLAVE PROTOCOL
10:48
1/1
Slave Protocol
+
IEC61850
- 564 -
6F2S1931 (0.20)
SLAVE PROTOCOL
10:48
1/4
IEC61850
IEC103†
DNP3.0†
Modbus†
)
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)