Toshiba GR200 Series Instruction Manual page 564

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Figure 10.3-12 DataSet list
As shown in the above figure, "Prot/EF_PTOC1$Str1, general" is already
mapped in the Dataset "STAT1".
3. To check, if the DataSet is already assigned to RCB, Right click on
select Edit Report Control, then Report Control List screen appears as shown in
Figure 10.3-13
.
Figure 10.3-13 Report Control List
As shown in the above figure, the DataSet "STAT1" is already assigned to
RCB "brcbST-A".
- 550 -
6F2S1931 (0.20)
"LLN0" and
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)