Toshiba GR200 Series Instruction Manual page 716

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Figure 11.8-11 shows selection of IO#2 (Slot #2).
Figure 11.8-11 Setting menu for Slot #2 module
Figure 11.8-12 shows the Output Circuit configuration of BO01 at IO#2 (Slot#2).
The procedure for operation is similar to the operation of the binary input circuit.
(Refer to Figure 11.8-7 to Figure 11.8-9)
Figure 11.8-12 Setting menu after selecting "SLOT2-BO01-SET"
The user can configure the required settings for the simulation test of the binary
output circuit.
ON:
OFF:
Normal:
TestFlag-EN screen
(iii)
This function can set all communication protocol Test flags to Test mode. The user should select
TestFlag-EN in Figure 11.8-1 and select On or Off.
Binary Output
10:48
Slot#2
Slot#3
Figure 11.8-10 Binary output menu
Slot#2
10:48
BO2F OP
SLOT2-BO01-SET
Normal
SLOT2-BO02-SET
Normal
SLOT2-BO02-SET
SLOT2-BO01-SET
10:48
Normal
Off
On
Output signal for simulation test is ON
Output signal for simulation test is OFF
Actual inputs are applied.
- 702 -
1/2
>
>
1/19
+
+
+
+
1/3
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)