Toshiba GR200 Series Instruction Manual page 43

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

The user has to make the coordination between the setting [DIF**-Slope] and CT
characteristics operating in the busbar. As shown in Figure 2.1-9, the switch [CTSC**-EN]† is
provided for blocking the DIF relay operation by CTSC. The user can halt the blocking the DIF
operation by CTSC using the [CTSC**-EN]=Off. The switch can be also available to test the
ratio of DIF characteristic.
DIF Relay element
Id
Setting [DIF**-I]
Detection of no change
Id
Setting [DIF**-I]
Figure 2.1-9 Configuration to block the DIF relay operation by CTSC
†Note: Asterisks (**) in settings here represent the general terms of "Check zone
protection (CH)" and "Discriminating zone protection (DZ)".
Operating area
Slope ratio=30%
Ir
Slope ratio=15%
Operating area
Ir
[CTSC**-EN]
On
- 29 -
6F2S1931 (0.20)
DIF relay operating signal without blocking by CTSC.
This signal can be used for testing.
DIFCH-A,B,C-TH
DIFZA-A,B,C-TH,
DIFZB-A,B,C-TH,
|
DIFZF-A,B,C-TH,
&
DIF relay operating signal
DIFCH-A,B,C
DIFZA-A,B,C
DIFZB-A,B,C
|
DIFZF-A,B,C
&
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)