OPT2 modules (OPT2)
4.3.4
It operates for the Main-SubUnit communication. The '
LAN for Local PC
' of MainUnit has two OPT2s. The SubUnit has an OPT2, and the user has
to set the ID number of a SubUnit.
MainUnit
SW
MainUnit
RX
0
TX
Figure 4.3-12 OPT2 module in MainUnit and SubUnit
Table 4.3-4 OPT2 communication between MainUnit and SubUnit
Module
Connector
Medium
Usage
Symbol
For SubUnit#1, the user should set '0' using Rotary switch (SW).
Notice
Similarly, set '1' on the OPT2 of SubUnit#2.
SubUnit#1
Optical transceiver
ST type
Fiber optic(GI)
Communication between MainUnit and SubUnit
OPT2 for MainUnit
Main-Sub
Communications
RX
TX
- 274 -
Max. Dual Ports
OPT2
Main-Sub
communication
RX
0
SubUnit#1
TX
Main-Sub
communication
SubUnit#2
RX
TX
0
SubUnit#2
MainUnit
OPT2 for SubUnit
SW
0
RX
TX
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
Dual Ports with
' and '
SW
RX
0
TX