Advertisement

Outline
The monitoring function is provided to measure the number of power quantities and statistics
data obtained within the VCT and BI circuits†. When the measuring instruments start
measures power quantities, mathematical means is applied to the data from the VCT so that
the data are shown accurately on the IED screen. The monitoring function has several screens
together. For current (I) and voltage (V) at rated input, the analog input data is measured with
±0.5% accuracy. For frequency, the data is measured with ±0.03% accuracy.
Metering data (Metering group)
Several abbreviations are screened for metering data, which shown in the below Table.
Abbreviations
DIFCH: Ida, Idb, Idc
DIFZA:
IdaA, IdbA, IdcA
DIFZB:
IdaB, IdbB, IdcB
DIFZC:
IdaC, IdbC, IdcC
DIFCH: Ira, Irb, Irc
DIFZA:
IraA, IrbA, IrcA
DIFZB:
IraB, IrbB, IrcB
DIFZC:
IraC, IrbC, IrcC
ZoneA:
VaA, VbA, VcA / VabA, VbcA, VcaA
ZoneB:
VaB, VbB, VcB / VabB, VbcB, VcaB
ZoneC:
VaC, VbC, VcC / VabC, VbcC, VcaC
ZoneA:
V1A, V2A, V0A
ZoneB:
V1B, V2B, V0B
ZoneC:
V1C, V2C, V0C
Respective CHs:
Ia, Ib, Ic
Respective CHs:
I1, I2, I0
fA, fB, fC, fD, fE, fF
f
Table 8.2-1 Metering data
DIFZD:
IdaD, IdbD, IdcD
DIFZE: IdaE, IdbE, IdcE
DIFZF:
IdaF, IdbF, IdcF
DIFZD:
IraD, IrbD, IrcD
DIFZE:
IraE, IrbE, IrcE
DIFZF:
IraF, IrbF, IrcF
ZoneD:
VaD, VbD, VcD / VabD, VbcD, VcaD
ZoneE:
VaE, VbE, VcE / VabE, VbcE, VcaE
ZoneF:
VaF, VbF, VcF / VabF, VbcF, VcaF
ZoneD:
V1D, V2D, V0D
ZoneE:
V1E, V2E, V0E
ZoneF:
V1F, V2F, V0F
- 424 -
6F2S1931 (0.20)
Displayed quantities
Magnitude of phase differential
current (Id) of Check-zone-relay
(DIFCH) and Discriminating-
zone-relay (DIFZA to DIFZF)
Magnitude of restraint current
(Ir) of Check-zone-relay (DIFCH)
and Discriminating-zone-relay
(DIFZA to DIFZF)
Magnitude and phase angle of
phase and phase-to-phase
voltage (V) in each zone
Magnitude and phase angle of
symmetrical component voltages
(V1, V2, and V0) in each zone
Magnitude and phase angle of
phase currents (Ia, Ib, Ic) in
each CH
Magnitude and phase angle of
symmetrical component currents
(I1, I2, I0) of each CH
Frequency calculated based on
the voltage in each zone
Frequency calculated based on
the current
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)