Toshiba GR200 Series Instruction Manual page 373

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Event recorder
Signals are generated in the logics of BIO modules etc. in the IED. The event recorder can
memory the generated signals as events. To operate the event recorder, the user should pick a
preferred signal as a trigger of the event recorder; the event recorder can have 768 triggers,
some of which have been set as a default. The user can group the triggers into three categories;
consequently, it is possible that a number of the events are divided depending on the degree of
the errors, the meaning of the operations, and the signals of relay elements, etc. The user can
also program how an event is to be detected. An event is recorded with millisecond accuracy.
The information are memorized until the number of the events reaching 1024; the oldest event
will be deleted when a new event appears.
Trigger signals
7.2.1
The event is memorized when the event recorder detects changing the trigger signal that is
connected with the logic signal; they are defined using settings [Trigger ID1] to [Trigger ID768].
Settings [End of E.Record-1] and [End of E.Record-2] are provided for grouping†; the user can
adjust the size of the 'Event Record1' group using the [End of E.Record-1]. The next 'Event
Record2' group is set with the [End of E.Record-2]. The remains are set for the 'Event Record3'
group. Remember that the [Trigger ID1] etc. are required to set together with the [Event
Name1] etc.; user's preferred names should be less than 18 letters.
Setting [End of E.Record-1] = 256
Setting [End of E.Record-2] = 512
3000001001
FR_CLR
FAULT RECORD (200602)
Setting [Trigger ID14]
= 200602 3000001001
Setting [Trigger Mode14]
= On
Setting [Event Name14]
= F.Record clear
3010001001
SYS_CHG
Setting_PF (201400)
Setting [Trigger ID7]
= 201400 3010001001
Setting [Trigger Mode7] = Change
Setting [Event Name7]
= Set group change
Figure 7.2-1 Relation between function signals and triggers for Event record1
Figure 7.2-1 illustrates signals connected with triggers in the event recorder. For example,
'SYS_CHG' is connected with trigger#7 using the [Trigger ID7] and 'FR_CLR' is connected with
July 25, 2012
10:31:12 Deleting the fault record
10:56:12 Changing system setting
On
Event #3
Active group
Active group
'3'
Changed to '4'
Event #2
- 359 -
6F2S1931 (0.20)
July 26, 2012
12:34:51 Deleting the fault record
Pulse train
List of 'Event record1'
Event #3
2012-07-25 10:31:12
F.Record clear 'On'
Event #2
2012-07-25 10:56:12
Set group change
Event #1
On
2012-07-26 12:34:51
Event #1
F.Record clear 'On'
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)