Toshiba GR200 Series Instruction Manual page 131

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Operation of EFP-trip
2.5.1
Based on the placement of CT and CB, the EFP function is grouped into three modes: (i) EFP
Zone-trip (Mode 1), (ii) EFP Transfer-trip (Mode 2), and (iii) Non EFP-trip. Using scheme
switches [EFP-EN_CH*], the user can select either On-Zone (Mode 1)/ On-TR (Mode 2)/ Off.
Operation of EFP Zone-trip (Mode 1)
(i)
Suppose a CB (CB-A) is placed at the line side and the bus-bar is operated while CB-A is in the
open position. Figure 2.5-1 shows a case that a fault occurs between the CB-A and the CT, so
that the DIF relay does not operate. To solve this problem, the EFP function is effective. Figure
2.5-2 illustrates two CBs (CB-B in Zone A and CBC used to connect the bus-bars) are tripped
to open by the EFP Zone-trip operation. For the operation in Mode1, set On-Zone for the
settings [EFP-EN_CH*] in respective CHs.
Remote
end
Remote
end
Line
CB-A
Figure 2.5-1 Fault occurrence and current flow before
tripping
Line
CB-A
Figure 2.5-2 Tripping CB-B and CBC by EFP
- 117 -
Busbar
Zone A
Fault
CT
CB-B
CBC
Busbar
Fault
Zone A
CT
CB-B
CBC
6F2S1931 (0.20)
Busbar
Zone B
Busbar
Zone B
CB closed
CH
CB open
CT
CB tripped
CBC Coupler-CB
DS closed
DS open
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grb200

Table of Contents