description: Binary IO Module
Figure 11.8-5 Binary input menu
Figure 11.8-6 is a case when IO#3 (Slot#03) is selected.
Slot#3
10:48
Figure 11.8-6 Setting menu for Slot #3 module
For example, if the user wishes to simulate binary input circuit #1 (BI1) on the
BIO1A module at IO#3 slot, the user can select SLOT3-BI01-SET screen, as shown
in Figure 11.8-6).
Figure 11.8-7 Setting menu after selecting "Slot #3-BIO1-SET"
The user can then make the following selections on the screen and configure the
items required for simulation.
ON:
BI1 output is set forcibly to ON(Logic level=high(1)) regardless of
the actual input signal.
OFF:
BI1 output is set forcibly to OFF(Logic level=low(0)) regardless of
the actual input signal.
Normal:
Actual inputs are applied.
Use the screen shown in Figure 11.8-7 only to configure the BI signals for the
)
Binary Input
10:48
1/2
Slot#1
>
Slot#3
>
1/19
BIF OP
+
Slot3-BIO1-SET
+
Normal
Slot3-BIO2-SET
+
Normal
Slot3-BI03-SET
+
Slot3-BIO1-SET
10:48
1/3
Normal
Off
On
- 700 -
6F2S1931 (0.20)
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)