Toshiba GR200 Series Instruction Manual page 47

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

input
.
As cited earlier, the discriminating-zone-protection can have up to six protection-zones,
but the setting of the minimum operating current (minDIF-I) is common to each protection-
zone. The user can set minDIF-I using the setting [DIFCH-I] and [DIFDZ-I].
When DIF trip and DIF transfer-trip need to operate securely, set On for setting [DIFTP-
FS]; then the DIF trip will be issued with the Fail-safe operation (FS). On the other hand, DIF
trip and DIF transfer-trip operate without the FS operation when Off is set for the setting
[DIFTP-FS].
Point for deciding about [DIF**-I] setting value
(iii)
To seek the [DIF**-I] setting value, the user should follow on the Step1 to the Step4:
Step 1: Minimum fault current (I Fmin )
The DIF operation should be ruled to be less than a minimum fault current multiplied
by 0.8. As a result, the DIF relay is able to operate on the minimum fault current. Equation
(2.1-6) illustrates the relation between the I Fmin and the [DIFCH-I] and [DIFDZ-I].
The DIF relay operates faster when the large fault current flows. Therefore, the value of
the I Fmin should be considered to be more than 300% of setting [DIF**-I], as shown in Equation
(2.1-7):
Step 2: Operation accuracy in the DIF relay
The operation accuracy depends on the primary value of the CT. The user should note
that the operation accuracy gets worse when the operating value in the DIF relay is small and
the
CT
primary
Setting [ DIF**-I ]
CT primary value
depends on the number of CHs.
Setting [DIF**-I] ≤ 0.8 × I
Setting [ DIF**-I ] ≤
value
is
large.
That
is small, as shown in Figure 2.1-12; the operation accuracy
- 33 -
Fmin
I
Fmin
3 ⁄
is,
the
accuracy
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
(2.1-6)
(2.1-7)
deteriorates
when

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grb200

Table of Contents