Toshiba GR200 Series Instruction Manual page 799

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

12.
PIXIT FOR GOOSE SUBSCRIBE MODEL
ID
Ed
What elements of a subscribed GOOSE
message are checked to decide the message is
valid and the allData values are accepted? If
yes, describe the conditions.
Notes:
the VLAN tag may be removed by a
ethernet switch and shall not be
checked
Gs1
1,2
the simulation flag shall always be
checked (Ed2)
When is a subscribed GOOSE marked as lost
(TAL = time allowed to live value from the last
received GOOSE message)
Gs2
1,2
What is the behaviour when one or more
subscribed GOOSE messages isn't received or
syntactically incorrect (missing GOOSE)
Gs3
1,2
Description
- 785 -
Value / Clarification
Y
destination MAC address
= as configured
Y
APPID
Y
gocbRef
N
timeAllowedtoLive
N
datSet
Y
goID
=as configured
N
t
N
stNum
Y
sqNum
Y
simulation / test
N
confRev
Y
ndsCom
N
numDatSetEntries
N
out-of-order dataset
members
[message does not arrive prior to
TAL]
GOOSE subscribe quality
information will become
QUESTIONABLE (=1100 0000
0000 0).
GOOSE status change is
accepted . The behavior can be
changed by modifying PLC
logic.
N
Substituted
Y
Test
N
OperatorBlocked
* Supports only for GBU DCAI
Model
[stNum is out-of-order, or missed]
No fail will be detected.
[sqNum is out-of-order, or missed]
GOOSE subscribe quality
information will become
QUESTIONABLE |
INCONSISTENT (=1100 0000
1000 0). After receiving message
with correct sqNum order, the
quality information is set to
GOOD (=0000 0000 0000 0).
You can assign the information to
any data attribute using our
configuration tool.
GOOSE status change is ignored
The behavior can be changed by
modifying PLC logic.
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
(PIXIT Ed.1&Ed.2)