Toshiba GR200 Series Instruction Manual page 152

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

6F2S1931 (0.20)
Figure 2.6-3 Inverse-time-reset characteristics curves
Figure 2.6-4 illustrates that an integrating value will be influenced dependent on the
DEP or DEF setting. An energized quantity (I), where I is greater than a threshold setting
[OC1], will make an integrating value, which can determine how the element operates. If the
energized quantity (I) falls below the threshold setting [OC1], the element operation will
return to its reset stage after the time t(I) calculated in Equation (2.6-2).
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
- 138 -