4.1.4 Specifications
Item
Number of Channels
AI Types Supported
Input Converter Resolution
I/O Scan Time
Input Accuracy
Noise Suppression on Inputs
Common Mode Rejection
Common Mode Voltage Range
Output Converter
Output Load
Output Accuracy
Power Consumption
Compressor Stall Detection
Size
Ambient Rating for Enclosure Design
Technology
Note For further details, refer to the Mark VIeS Functional Safety Analog I/O Module Summary Sheet (GEI-100866).
96
GEH-6855_Vol_II

YAIC Specification

12 channels per terminal board (10 AI, 2 AO)
Inputs 1 to 8: ±5 V dc, ±10 V dc, or 4–20 mA
Inputs 9 to 10: 4–20 mA or ±1 mA
16-bit ADC
Supported Controller I/O Scan rates: 10 ms, 40 ms, 80 ms, 160 ms
0.1% of full scale over the full operating temperature range.
The 10 circuits have hardware filter with single pole down break at 500 rad/s. A software filter,
using a two pole low pass filter, is configurable for: 0.75 Hz, 1.5 Hz, 3 Hz, 6 Hz, 12 Hz
AC CMR 60 dB at 60 Hz, with up to ±5 V common mode voltage.
DC CMR 80 dB with -5 to +7 peak V common mode voltage
±5 V (±2 V CMR for the ±10 V inputs)
14-bit D/A converter with 0.5% accuracy
800 Ω max for 0-20 mA output
±0.5% of full measurement range
5.3 watts typical, 6.2 watts worst case
Not supported
8.26 cm high x 4.19 cm wide x 12.1 cm deep (3.25 in x 1.65 in x 4.78 in)
-40 to 70°C (-40 to 158 °F)
Surface mount