Outputs Unhealthy On Ionet - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

1008-1010,
1264-1266
Description
Outputs unhealthy on IONet [ ] - Message Timeout
Possible Cause
Controller is rebooting or has rebooted
Application/configuration does not match in I/O pack or module and controller.
Failed Ethernet connection between the I/O pack or module and the controller.
Solution
Reset all diagnostic alarms.
Rebuild and download the application to all the processors, including I/O packs or modules.
Reload the firmware and the application.
Verify that the Ethernet cable on the I/O pack or module matches the ToolboxST configuration.
Check for a faulty Ethernet cable from the I/O pack or module to the network switch and/or from the switch to the
controller. Replace cable(s) if necessary.
Replace the I/O pack or module.
Faulty network switch; place the I/O pack or module's Ethernet cable into an empty port. If the problem persists, replace
the network switch.
1008-1010,
1264-1266
Description
Outputs unhealthy on IONet [ ] - Message Length not valid
Possible Cause
Application/configuration does not match in I/O pack or module and controller
Solution
Rebuild and download the application/parameters to all controllers and I/O packs or modules.
Reload the firmware and parameters to the affected I/O pack or module.
Reload the firmware and the application to all controllers.
If the problem persists, replace affected I/O pack or module, then replace the controller.
1008-1010,
1264-1266
Description
Outputs unhealthy on IONet [ ] - Major Signature Mismatch
Possible Cause
Application/configuration does not match in I/O pack or module and controller
Solution
Rebuild and download the application/parameters to all the controllers and I/O packs or modules.
Reload the firmware and the parameters to the affected I/O pack or module.
Reload the firmware and the application to all controllers.
If the problem persists, replace affected I/O pack or module, then replace the controller.
474
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II