Jpdc-Fuse Fu1T Or Fu2T (J1T Connector) Is Blown Or Sw1T Switched Off; Input Src Mismatch On Jpdc: Ac Src Detected At Input Instead Dc - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

179
Description JPDC-Fuse FU1T or FU2T (J1T connector) is blown or SW1T switched OFF.
Possible Cause
The specified switch is turned off and FuseDiag is enabled.
The specified fuse is blown.
The 125 V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 125 V dc input connections to the terminal board.
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
180
Description Input Src Mismatch on JPDC: AC src detected at input instead DC.
Possible Cause
The ac voltage has been detected at the 125 V dc input.
Solution
Verify the 125 V dc input connections. Use a DVM to verify the dc voltage on the input connections.
Verify that the positive and negative inputs to the 125 V dc bus are connected to the proper terminals. Refer to the JPDC
help documentation.
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
PDM Power Distribution Modules
Public Information
GEH-6855_Vol_II System Guide 349