Hart_Enable
Hart_CtrVars
Enable Hart protocol on
Number of control vars to
this channel
read from Hart device
Set to zero if not used.
{Disable}
{0}
Enable
0-5
The first time any channel 1–8 is enabled, the I/O pack will require a reboot. The first time any channel 9–16 is enabled, the I/O
pack will require a reboot.
The first time all channel 1–8 are disabled, the I/O pack will require a reboot. The first time all channel 9–16 are disabled, the
Attention
I/O pack will require a reboot.
204
GEH-6855_Vol_II
Current Outputs (continued)
Hart_ExStatus
Hart_MfgID
Hart Field Device -
Number of extended status
bytes to read from Hart
Manufacture ID
device
Note: For HART7 field
Set to zero if not used.
devices, this is the upper
byte of Expanded Device
Type
A diagnostic alarm is sent
if the field device ID differs
from this value and the
value is non-zero. This
value can be uploaded
from the YUAA if the field
device is connected.
(Right-click on device
name and select Update
HART IDS)
{0}
{0}
0-26
0-255
Public Information
Hart_DevType
Hart Field Device - Device
Type
Note: For HART7 field
devices, this is lower byte
of Expanded Device Type
{0}
0-255
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Hart_DevID
Hart Field Device - Device
ID
{0}
0-116777215