Auto-Reconfiguration Server Installation Is Incomplete; Auto-Reconfiguration Server Failed Scanning Or Downloading An I/O Pack; Could Not Configure Consumed Exchanges From One Or More Producers - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

486
Description Auto-Reconfiguration server installation is incomplete
Possible Cause
A download from the ToolboxST application to an I/O pack and/or the Auto-Reconfiguration server has failed
Not all of the I/O packs were selected for download
Solution Perform a scan and download using the ToolboxST application.
487
Description Auto-Reconfiguration server failed scanning or downloading an I/O pack
Possible Cause At least one I/O pack is in an unexpected state that the Auto-Reconfiguration server is unable to handle
Solution
Cycle power on the I/O pack.
Perform a scan and download using the ToolboxST application.
Replace the I/O pack.
488
Description EGD Error - Could not configure consumed exchanges from one or more Producers
Possible Cause
Producer EGD Page(s) configured incorrectly
Producer(s) powered down
Network connectivity intermittent or severed
Internal Firmware failure
Solution
Rectify configuration error. Compress all pages and download application to Producer.
Ensure each Producer is powered on and in the Controlling state.
Refer to the Network Troubleshooting guide for possible solutions.
Replace the Consumer and/or Producer hardware.
Controllers
Public Information
GEH-6855_Vol_II System Guide 61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents