262
Description

Bad configuration file detected

Possible Cause
During commission/maintenance:
The configuration file in the I/O pack or module is not compatible with loaded application code
During normal operation:
There is a hardware failure
Solution
During commissioning or maintenance:
Rebuild the system and download the application and the configuration to the I/O pack or module.
During normal operation:
Replace the I/O pack or module.
263
Note This alarm is obsolete.
Description

Invalid configuration file

Possible Cause
During commissioning or maintenance:
The downloaded configuration file is for a different type of I/O module.
During normal operation:
There is a hardware failure.
Solution
During commissioning or maintenance:
Rebuild the control system and download the application and configuration to the I/O module.
During normal operation:
Replace the I/O pack.