Jpdg-P28V Volt Fdbk (Jr/Js Connector) Out Of Range.; Jpdg-P28V Dry Contact Input [ ] (P3 Connector) Not Ok; Jpdg Fuse Fu1 (J1 Connector) Is Blown; Jpdg Fuse Fu2 (J1 Connector) Is Blown - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

195
Description

JPDG-P28v volt fdbk (JR/JS connector) out of range.

Possible Cause
The 28 V power supply input is out of range. It should be within ± 5% of 28 V.
The 28 V power supply has not been connected.
There may be a power supply problem.
Solution
The input is not used. Set the PS28v Enable to Disable.
Check the power supply connections (specified connector) to the terminal board.
From the ToolboxST application JPDG Inputs tab, verify that the power supply feedback configuration is within the
expected tolerance (± 5%).
196 – 197
Description JPDG-P28v dry contact input [ ] (P3 connector) not OK
Possible Cause
The power supply contact is open. The power supply is not operating normally.
The power supply contact feedback is not connected to the specified terminal board connector.
The power supply dry contact is not used.
Solution
Verify the status of the power supply contact, and that the power supply is operating correctly.
Check the connections between the power supply and the specified connector on the JPDG.
If the input is not used, set the PS28v Enable to Disable.
If the power supply is used but the dry contact feedback is not connected, set the PS28vEnable to NoDryCnt to disable
this alarm. Continue to monitor the 28 V power supply input.
198
Description JPDG fuse FU1 (J1 connector) is blown
Possible Cause The specified fuse is blown.
Solution Replace the fuse.
199
Description JPDG fuse FU2 (J1 connector) is blown
Possible Cause The specified fuse is blown.
Solution Replace the fuse.
356
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information