Jpdd Cabling - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

10.4.1 Installation
JPDD is held in a plastic holder, which mounts on a vertical DIN-rail. When installing the JPDD, it is important to provide a
ground lead from TB1 to the system ground. This creates a ground path for the metal switch bodies.

JPDD Cabling

Power input can be 24 V dc, 48 V dc, or 125 V dc, but only one voltage level at any given time. Do not mix voltages. For
cable destinations, refer to the circuit diagram. TB1 should be connected to system ground.
PDM Power Distribution Modules
GEH-6855_Vol_II System Guide 363