GE Mark VIeS System Manual page 345

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

170-171
Description Input Src Mismatch on JPDF-[ ]: AC src detected at input instead DC.
Possible Cause
The ac voltage has been detected at the 125 V dc input.
Solution
Verify the 125 V dc input connections. Use a DVM to verify dc voltage on the input connections.
Verify that the positive and negative inputs to the 125 V dc bus are connected to the proper terminals. Refer to the JPDF
help documentation.
172
Description JPDC-DC 125V fdbk mag (JD1/JZ2 connector) out of range.
Possible Cause
The 125 V dc input is less than DC_125v_Trig_Volt.
DC_125v_Trig_Volt is set too high.
The 125 V dc source voltage is out of range.
The 125 V dc input is not connected.
Solution
Verify that DC_125v_Trig_Volt is set correctly.
If fed from the dc battery input, check the connections to JD1 and TB1.
If fed from DACA, check the connections to JZ2.
Verify the grounding of dc input signals. Refer to the JPDC help documentation.
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
PDM Power Distribution Modules
Public Information
GEH-6855_Vol_II System Guide 345