Description Intermittent Communications on IONet1 – Packet Loss Exceeded [ ]%
Possible Cause
Power cycled on I/O producer (controller or I/O module)
Faulty Ethernet cable from I/O pack to IONet switch and/or from IONet switch to controller.
Faulty IONet switch
I/O message corruption
Communication errors occurred on more than 5% of data transmissions on IONet1
Solution
Check for evidence of I/O pack restart (diagnostic alarms, error logs).
Replace Ethernet cable(s).
Replace the I/O pack.
Move the I/O pack's Ethernet cable into an empty IONet switch port. If problem persists, replace the IONet switch.
349
Description Intermittent Communications on IONet2 – Packet Loss Exceeded [ ]%
Possible Cause
Power cycled on I/O producer (controller or I/O module)
Faulty Ethernet cable from I/O pack to IONet switch and/or from IONet switch to controller.
Faulty IONet switch
I/O message corruption
Communication errors occurred on more than 5% of data transmissions on IONet2
Solution
Check for evidence of I/O pack restart (diagnostic alarms, error logs).
Replace Ethernet cable(s).
Replace the I/O pack.
Move the I/O pack's Ethernet cable into an empty IONet switch port. If problem persists, replace the IONet switch.
350
Description Intermittent Communications on IONet3 – Packet Loss Exceeded [ ]%
Possible Cause
Power cycled on I/O producer (controller or I/O module)
Faulty Ethernet cable from I/O pack to IONet switch and/or from IONet switch to controller.
Faulty IONet switch
I/O message corruption
Communication errors occurred on more than 5% of data transmissions on IONet3
Solution
Check for evidence of I/O pack restart (diagnostic alarms, error logs).
Replace Ethernet cable(s).
Replace the I/O pack.
Move the I/O pack's Ethernet cable into an empty IONet switch port. If problem persists, replace the IONet switch.