Tvba Vibration Input; Tvba Compatibility And Attributes; Tvba Installation, Operation, And Jumper Configuration; Accelerometers With Integrated Outputs - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

8.5 TVBA Vibration Input

The Vibration Input (IS410TVBAS2B) terminal board acts as a signal interface board for the Mark VIeS YVIB I/O packs.
The TVBA provides a direct vibration interface to Eddy-current (position & velocity), seismic (velocity), Velomitors
(velocity) and accelerometers with integrated outputs (velocity) sensors. The TVBA also provides a dynamic pressure
interface to charge amplifiers.
The terminal board input signals entering through the two 24-point screw terminals are protected against high voltages due to
electrical disturbances via transient suppression. Powering the different sensors and detecting open circuits is accomplished
by jumpers JPxA located to the left of the 37-pin I/O pack connectors and JPxC located to the right of the 24-point screw
terminals.
The input signals are passed on to the I/O packs through 37-pin connectors located on the right side of the TVBA. The TVBA
can be used for either simplex or TMR applications. TMR applications fan the signal to three I/O packs.
Buffered outputs of the input signals are provided to 9 and 25 pin DIN connectors to feed the Bently Nevada* 3xxx
monitoring system. A bayonet nut connection (BNC) connection for each buffered output is also included to feed third party
monitoring equipment. To configure the output buffers for the proper sensor, use the JPxB jumpers that are located to the left
of the 37-pin I/O pack connectors. The I/O pack inputs channels 1 through 13 and channels 1 through 14 are routed to
buffered outputs for external use. These BNC and DIN connectors, and the jumper are only available on TVBAH2A,
TVBAH2B, TVBAS2A, and TVBAS2B.
Power is obtained from customer supplied +28 V through the I/O pack.

8.5.1 TVBA Compatibility and Attributes

The I/O pack works with the TVBA terminal board to provide all sensor input checks. The following terminal board revisions
work with the I/O pack.
Compatibility
Terminal Board
TVBAS2B
YVIBS1A and YVIBS1B
Mixing I/O pack revisions on a TMR module does not allow for Enhanced mode of operation.
N28 power is generated internally to TVBAS2B.

8.5.2 TVBA Installation, Operation, and Jumper Configuration

The TVBA accepts 14 sensor inputs that are wired directly to two 24-point I/O terminal blocks. Each block is held down with
two screws accepting up to #12 AWG wires. A shield termination attachment point is located adjacent to each terminal block.
The I/O pack can only process 13 of the 14 channels. The 14th channel is forwarded to the buffered output stage for use by
the Bently Nevada equipmen.

8.5.2.1 Accelerometers with Integrated Outputs

The TVBA supports accelerometers with integrated outputs on channels 1, 2 and 3 only when the Tracking filters are
required. If broadband rms vibration is all that is required, then all eight channels are available to use. For example, Oil & Gas
LM1600, LM2500 or LM6000 gas turbine applications use the Bently Nevada 86517 sensor. The 86517 is powered by -24 V
and the velocity output is connected to the vibration inputs: PRxxH and PRxxL. Tie the shield on the Mark VIeS end and
leave the shield open on the sensor side preventing ground loops.
276
GEH-6855_Vol_II
Buffered Output
WNPS
Circuits, DIN, and
Connectors
BNC Connectors
Yes
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information
IEC61508
Safety Certified
No
Yes
Allows Mixing of I/O
Pack Revisions
No

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents