7.12.6 Digital Inputs
Digital Inputs SignalInvert
Description
Inversion makes signal
true if contact is open
Choices
{normal}
{defaults}
Invert
206
GEH-6855_Vol_II
SeqOfEvents
LineMonitoring
Record contact
Open/shorted input detection
transitions in
sequence of events
Does not apply when InputMode
is set to NAMUR, as line
monitoring is inherent in NAMUR
operation.
{Disable}
{Disable}
Enable
Enable
InputMode
SignalFilter
Internal/ExternalWet-
Contact input filter
ting, NAMUR Sensor
in milliseconds
{Internal}
{Unfiltered}
External
10 ms
NAMUR
20 ms
50 ms
100 ms
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information
ExtWettingVoltage
External wetting voltage
Only applicable if InputMode is
set to External Wetting
{24.0}