121, 130
Description JPDF-[ ] fuse FU75 or FU76 (J7Z connector) is blown or SW7Z switched OFF.
Possible Cause
The SW7Z is turned off and FuseDiag is enabled.
The FU75 or FU76 fuse is blown.
The 125 V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 125 V dc input connections to the terminal board.
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
122, 131
Description JPDF-[ ] fuse FU81 or FU82 (J8A connector) is blown.
Possible Cause
The FU81 or FU82 fuse is blown.
The 125 V dc input is not connected.
Solution
Replace the fuse.
Verify the 125 V dc input connections to the terminal board.
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.