264
Note This alarm is obsolete.
Description Firmware/Configuration Incompatibility Error
Possible Cause
I/O pack or module configuration files are incompatible with the firmware.
The files have the wrong revision.
Solution
Confirm the correct installation of the ToolboxST application.
Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack and selecting
Upgrade.
Rebuild the application, and download the firmware and application code to the affected I/O pack or module.
265
Description

Configuration file load error - invalid I/O header size

Possible Cause
During commissioning or maintenance:
Build error
Controller EGD revision code is not supported
Incompatible version of the I/O pack or module firmware was downloaded
During normal operation:
There is a hardware failure.
Solution
During commissioning or maintenance:
Confirm the correct installation of the ToolboxST application.
Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack and selecting
Upgrade.
Rebuild the application, and download the firmware and application code to the affected I/O module.
During normal operation:
Replace the I/O pack or module.
454
GEH-6855_Vol_II