Voltage
Applicable
Inverter type-form
class
motor (kW)
3-phase
0.4
VFAS3-
480 V
0.75
1.5
2.2
4.0
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
220
280
Input current (A)
4004PC
0.9
4007PC
1.8
4015PC
3.2
4022PC
4.9
4037PC
8.3
4055PC
10.9
4075PC
14.7
4110PC
21.4
4150PC
28.9
4185PC
35.4
4220PC
42.1
4300PC
57.1
4370PC
69.9
4450PC
84.8
4550PC
103.3
4750PC
139.8
4900PC
170.2
4110KPC
203.5
4132KPC
240.3
4160KPC
290.0
4200KPC
360.0
4220KPC
395.0
4280KPC
495.0
10-5
Rated current (A)
Molded-case circuit
breaker (MCCB)
Magnetic contactor
Earth leakage circuit
(MC)
breaker (ELCB)
3
3
5
10
10
15
20
30
40
50
60
75
100
125
125
175
225
250
300
350
500
500
700
10. Selection and installation of peripheral devices
E6582062
20
20
20
20
20
20
20
3
32
32
50
50
60
80
100
135
200
260
260
260
350
450
9
450
660
10