Example of 0 - 10 Vdc voltage input setting
Output frequency (Hz)
<F204>
(60Hz)
<F202>
(0Hz)
<F201>
Example of 4 - 20 mAdc current input setting
Output frequency (Hz)
4
<F219>
(60Hz)
5
<F217>
(0Hz)
<F216>
5) Setting the time elapsed before PID control starts
Waiting time until starting PID control system can be set to avoid PID control until the control
system becomes stable at power on.
The inverter ignores feedback input signals and runs at the frequency determined by the
9
frequency command value for the period of time set with <F369: PID1 start wait time>, and
enters PID control after the elapsed time.
Title
F369
5. [Fundamental operation] How to use parameters
Terminal [RR] input value
0V
10V
<F203>
0%
100%
Terminal [II] input value
4mA
20mA
<F218>
0%
100%
Parameter name
PID control start wait time
Example of -10 - +10 Vdc voltage input setting
Output frequency (Hz)
<F213>
(60Hz)
<F211>
(0Hz)
0V
<F210>
0%
Adjustment range
0 - 2400
5-58
E6582062
Terminal [RX] input value
10V
<F212>
100%
Unit
Default setting
s
0