6. 30. 17 Setting parts replacement alarm by the ambient
<F634: Annual average ambient temperature>
■ Function
4
Based on the inverter ON time (cumulative power ON time), motor run time (cumulative run time),
cooling fan run time (cumulative cooling fan run time), output current , and <F634: Annual average
4
ambient temperature>, the time of replacement of the cooling fan, power circuit capacitor, and
capacitor mounted on a printed circuit board is calculated. When the time of replacement
approaches, the alarm can be output on the monitor display and output terminal.
6
■ Parameter setting
Title
F634
9
■ Selecting a setting value
Set the annual average temperature around the inverter. (This is not the annual highest
temperature.)
Important
■ Signal output of parts replacement alarm
Assign the parts replacement alarm to the unused output terminal. For details, refer to [7. 2. 2].
"128: Parts replacement alarm"
"160: Cooling fan replacement alarm"
■ Monitor display of parts replacement alarm
Parts replacement alarm information (refer to [8. 1. 1]) can be checked in the [Monitor mode].
6. [Advanced] How to use parameters
temperature
Parameter name
Annual average ambient
temperature
• Set <F634: Annual average ambient temperature> when installing the inverter. After the
installation, this setting should not be changed. Otherwise, calculation of parts replacement
alarm may have an error.
F634
3: +21 to +30
4. +31 to +40
5. +41 to +50
6. +51 to +60
1. -15 to +10
Adjustment range
1: -15 to +10°C
2: +11 to +20°C
3: +21 to +30°C
4: +31 to +40°C
5: +41 to +50°C
6: +51 to +60°C
6-144
E6582062
STOP
0.0Hz
14:03
: Ambient temperature
Default setting
3