Toshiba TOSVERT VF-AS3 Instruction Manual page 432

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Host computer
INV
No.00
INV: Inverter
★ : Use the terminal block, etc. to branch the cable.
4
1. Data is sent from the host computer.
2. Data from the computer is received at each inverter and the inverter numbers are checked.
3. When "*" is added to the position of an inverter number, it is judged a broadcast. The
4
command is decoded and processed.
4. To prevent data conflicts, only inverters where "*" is overwritten to "0" can reply with data to
6
the host computer.
5. As a result, all inverters are operating with the broadcast operation frequency command.
Specify inverter numbers by group for group broadcasts.
This is a function only for ASCII mode. For parity mode, refer to RS485 Communications
Function Instruction Manual (E6582143).
For example, when "*1" is set, inverters "01", "02", "03", "04", ..., "09" can be broadcast to.
9
In this case, the inverter specified as "01" can reply.
■ Connection example of inverter-to-inverter communication
One inverter is a leader and the other inverters are followers.
Here is a case where all follower inverters connected operate at the same frequency as the leader
inverter.
No frequency point is set.
Leader inverter
INV
No.00
INV: Inverter
★ : Use the terminal block, etc. to branch the cable.
1. The leader inverter transmits frequency command data to its follower inverters.
6. [Advanced] How to use parameters
INV
INV
No.01
No.02
INV
INV
No.01
No.02
: Wiring
: Data (Host - INV)
: Response data (INV - Host)
INV
INV
No.03
No.29
: Wiring
: Data (Leader - Follower)
INV
INV
No.03
No.29
6-190
E6582062
INV
No.30
INV
Follower
No.30