Toshiba TOSVERT VF-AS3 Instruction Manual page 395

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

6. 30. 22 Setting cumulative overcurrent level and time
<F659: Cumulative overcurrent level>
■ Function
Inverter cumulates the time when motor current is over this parameter. This cumulative time can be
confirmed in [Monitor mode].
■ Parameter setting
Title
Parameter name
F659
Cumulative overcurrent
level
■ Signal output of the cumulative overcurrent time
You can confirm the cumulative overcurrent time in [Monitor mode].
Set the monitor numbers shown below to <F711: Monitor mode 1 display> to <F718: Monitor mode
8 display>. For details, refer to [8. 1. 1].
 "93: Cumulative overcurrent time"
• Cumulative overcurrent time can be confirmed in [Monitor mode]. You can reset the monitor
Memo
value to 0 with the setting of "15: Clear cumulative overcurrent time " in <tyP: Default setting>.
For details, refer to [5. 2. 9].
• How to operate the operation panel -> Refer to [3. 1. 1].
Reference
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
F659 : Cumulative overcurrent level
Min: 10
X1000
Adjustment range
10 - 200
6-153
E6582062
STOP
0.0Hz
14:06
100
%
Max: 200
X100
X10
X1
Unit
Default setting
%
100
6. [Advanced] How to use parameters
3
4
6
9