Toshiba TOSVERT VF-AS3 Instruction Manual page 344

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

2) In case of torque limit
4
4
If, during power running, the output torque reaches the value for <F441: Power running torque
limit level 1> or more, and continues for the period of time set for <F452: Stall detection time
during power running>, the trip "Ot2" will occur. In case F452=0, this function is not activated
6
(Ot2 trip does not occur).
Reference
9
6. [Advanced] How to use parameters
Output frequency (Hz)
Output torque (%)
<F441>
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
"0t2" Trip
Time (s)
Time (s)
Below
<F452>
<F452>
6-102
E6582062