Input terminal
S1-CC
OFF
ON
• Be sure to perform V/f switching in the stop state. Switching is impossible during run. It takes 0.1
second before switching. Therefore, be sure to wait 0.1 second or more after inputting a switching
4
signal, and then start operation.
• When you want to use the vector control and V/f 5-point setting, select V/f1. When V/f2 to V/f4 are
selected, V/f constant is obtained, and thus making the vector control impossible.
4
• When you use an input terminal where a variety of functions can be assigned, you can link the
switching of torque limit or acceleration/deceleration time to V/f switching.
6
For operation panel run, you can also set the acceleration/deceleration time at <F504: Panel Acc/
Dec select>. For details, refer to [6. 27. 2].
Reference
9
6. [Advanced] How to use parameters
V/f
S2-CC
Base frequency 3: <F174>
Base frequency voltage 3: <F175>
ON
3
Manual torque boost 3: <F176>
Motor overload protection current 3: <F183>
Base frequency 4: <F178>
Base frequency voltage 4: <F179>
ON
4
Manual torque boost 4: <F180>
Motor overload protection current 4: <F184>
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3].
• Details on operation by external signals -> Refer to [Chapter 7].
Parameters selected
6-18
E6582062
Output terminal
(function number)
No.186
No.188
OFF
ON
ON
ON