■ Online auto-tuning setting
<F403: Online auto-tuning> is a function that automatically adjusts motor parameters by predicting
the increase in motor temperature.
• Online auto-tuning must be performed along with <F400: Offline auto-tuning>.
• Perform auto-tuning when the motor has cooled down (same temperature as the ambient
temperature).
7) Parameter setting
Title
F403
4
8) Selecting a setting value
1: Self-cooling motor auto-tuning
Set this value when the motor is equipped with a self-cooling fan (a type in which a fan is
4
directly connected to the motor shaft).
6
2: Forced air-cooling motor auto-tuning
Set this value when the motor is equipped with a fan motor (forced air-cooling).
Reference
9
6. [Advanced] How to use parameters
Parameter name
Online auto-tuning
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
Adjustment range
0: Disabled
1: Self-cooling motor auto-tuning
2: Forced air-cooling motor auto-tuning
6-88
E6582062
Default setting
0