Toshiba TOSVERT VF-AS3 Instruction Manual page 400

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Output frequency
Example 1: <F660>= "0: Disabled", <F661>= "3: Terminal II"
<FMOd>= "1: Terminal RR", <FH>= "80.0", <UL>= "80.0"
4
terminal [RR] input
 <F201>= "0", <F202>= "0.0", <F203>= "100", <F204>= "80.0"
4
terminal [II] input
 <F216>= "0", <F220>= "0", <F218>= "100", <F221>= "100"
Output frequency = Reference frequency x {1 + Override (terminal [II] input (%)/100)}
6
Example 2: <F660>=0 (disabled), <F661>=1 (terminal [RR])
<FMOd>= "2: Terminal RX", <FH>= "80.0", <UL>= "80.0"
terminal [RX] input
<F210>= "0", <F211>= "0.0", <F212>= "100", <F213>= "80.0"
terminal [RR] input
<F201>= "0", <F205>= "0", <F203>= "100", <F206>= "100"
9
Output frequency = Reference frequency x {1 + Override (terminal [RR] input (%)/100)}
Example 3
Output frequency = Reference frequency x {1 + Override (<F729: Panel override multiplication gain>
Setting value (%)/100)}
Reference
6. [Advanced] How to use parameters
Frequency after override
<FH>
[RR] input
(Reference
frequency)
0
10V
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
• Details on operation by external signals -> Refer to [Chapter 7].
Output frequency
Frequency after override
<FH>
Fwd
-10V
0
<FH>
6-158
E6582062
[RX] input
(Reference
frequency)
10V
Rev