Encoder system connection
9.8 Sensor Module External SME20
9.8.6

Technical data

Table 9-29
Technical data
6SL3055-0AA00-5EA.
Electronics power supply
Voltage
Current (without encoder system)
Current (with encoder system)
Power loss
Max. cable length
Encoder system power supply
Voltage
Current
Encoder frequency that can be evaluated
(f
)
encoder
Protective ground conductor connection
Weight
Note
Current controller clock cycle
For a current controller clock cycle of 31.25 µs, an SME20 with article number
6SL3055-0AA00-5EA3 must be used.
The maximum cable length for the encoder system interface depends on the current
consumption of the encoder system and the cross-section of the wire in the cable. However, the
maximum length is 30 m. The figure below applies to encoder systems that operate in the supply
voltage range between 4.75 V and 5.25 V. The sample parameters shown are 0.28 mm² cross-
section (0.14 mm² supply plus 0.14 mm² Remote Sense wires) and 0.64 mm² (0.5 mm² supply
plus 0.14 mm² Remote Sense wires).
280
Unit
Value
V
24 (20.4 ... 28.8)
DC
A
≤ 0.15
DC
A
≤ 0.25
DC
W
≤ 4
m
30
V
5
DC
A
0.35
DC
kHz
≤ 500
At the housing with M4 screw
kg
0.31
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2