Voltage Sensing Module VSM10

8.10 Technical data

Use 2 screwdrivers or another suitable tool in order to relieve the strain on the holding springs
in the terminal, and then withdraw the connector jumper.
Terminal X530 with connector jumper
Electric shock when the connector jumper is removed
Because of the capacitors, a hazardous voltage is present at the X530 connector jumper for up
to 5 minutes after the power supply has been switched off.
Contact with live parts can result in death or serious injury.
• Wait 5 minutes after the supply has been switched off before removing the connector
8.10
Technical data
Table 8-10
6SL3053-0AA00-3AA1
Electronics power supply
Voltage
Current (without DRIVE-CLiQ)
Power loss
Maximum cable length
Protective ground conductor connection
Ventilation clearances, above/below
Weight
226
WARNING
jumper.
Technical data
Relieve the springs and withdraw the connector
jumper
Unit
Value
V
24 (20.4 ... 28.8)
DC
A
≤0.2
DC
W
≤4
m
30
On the housing with M4 screw
mm
50
kg
1
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2