X500 Drive-Cliq Interface - Siemens SINAMICS S120 Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Voltage Sensing Module VSM10
8.3 Interface description
X530
Neutral point grounding
Connector jumper
Figure 8-2
X530 interface at the VSM10 (view from below)
8.3.2

X500 DRIVE-CLiQ interface

Table 8-2
Connector
type
The blanking cover for the DRIVE-CLiQ port is included in the scope of delivery.
Blanking covers (50 x) Article No.: 6SL3066-4CA00-0AA0
216
X500: DRIVE-CLiQ interface
Pin
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)
DRIVE-CLiQ socket
PE conductor connection
M4 / 1.8 Nm
Technical data
Transmit data +
Transmit data -
Receive data +
-
-
Receive data -
-
-
Power supply
Electronics ground